top of page
GXT-1000MTPLUS230

GXT-1000MTPLUS230

$657.80Price
•Double conversion on-line technology
•Compact tower design
•Standard models and long backup models available
•Extended runtime capabilities by building up additional battery resources
•Flexible (site specific) battery configuration
•Standard model comes with internal battery
•Generator-compatible with wide input frequency range (40 to 70 Hz)
•0.8 output power factor
•Class A electromagnetic interference (EMC)
•Ultra wide input voltage range
•High input power factor & low THDi
•Emergency power off (EPO)
•Configurable to energy saving mode (ECO)
•LCD display for operational convenience and status / fault information
•Multiple AC output interfaces via IEC standard sockets with Programmable output
•Remote Monitoring is available through USB / RS232, and optional via dry contacts and SNMP
  • Details

    Capacity (VA/W)1000 / 8002000/16003000/2400
    Input Parameters
    Frequency Range40Hz ~ 70 Hz
    Phase Single phase with ground
    Power Factor≥ 0.99 @ 220 to 230 VAC (input voltage)
    Voltage Range
    Low Line Transfer160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
    ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
    Low Line Comeback175 VAC ± 5 %
    High Line Transfer300 VAC ± 5 %
    High Line Comeback290 VAC ± 5 %
    Output Parameters
    Output Voltage208/220/230/240VAC
    AC Voltage Regulation± 3% (Batt. Mode)
    Frequency Range47 to 53 Hz or 57 to 63 Hz (Synchronized Range)
    Frequency Range (Batt. Mode)50 Hz ± 0.25Hz
    Overload100% to 110%: audible warning
    110% to 130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass mode when the utility is normal.
    >130%: UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal.
    Current Crest Ratio3:1
    Harmonic Distortion≤ 3 % THD (Linear Load)
    ≤ 4 % THD (Linear Load)≤ 6 % THD (Non-linear Load)
    ≤ 7 % THD (Non-linear Load)
    Waveform (Batt. Mode)Pure Sinewave
    Efficiency
    AC Mode~ 85%~ 88%
    Battery Mode~ 83%
    Transfer Time
    AC Mode to Batt. ModeZero
    Inverter to Bypass4 ms (Typical)
    Battery Charger (Standard Model)
    Battery Type12 V / 7 AH12 V /7 AH12 V / 9 AH
    Numbers366
    Typical Recharge Time4 hours recover to 90% capacity (Typical)
    Charging Current1.0 A(max.)
    Charging Voltage41.0 VDC ± 1%82.1 VDC ±1%
    Battery Charger (Long back-up Model)
    Numbers38
    Charging Current4.0 A or 8.0 A(max.)
    Charging Voltage41.0 VDC ± 1%109.6 VDC ±1%
    Physical Parameters
    Dimension, D X W X H220 x 145 x 397318 x 190 x 421
    Net Weight (kgs)13726132813
    Emvironmental Parameters
    Operation Humidity20 to 90 % RH @ 0 to 40°C (non-condensing)
    Noise LevelLess than 55dBA @ 1 Meter
    Management
bottom of page